1/2" x 1/2" x 1/2" Notch Trowel
Below is an example of large tile installation using the 1/2” x 1/2” trowel that does not achieve the industry minimum mortar requirements of 80% coverage in dry areas.
This tile installation does not follow tile industry standards and best practices as found in ANSI A108.5.
• The mortar coverage and transfer does not meet the required 80% in dry areas.
• The mortar shown is troweled parallel to the long side, but it should be troweled parallel to the short side of the tile to facilitate air removal and collapsed ridges.
1/4"
1/4"
3/8" or 1/2"
1/4"
1"
1/4" x 3/8" or 1/4" x 1/2" SQUARE or U NOTCH TROWEL
MARSHALLTOWN.com
1.800.888.0127 1.800.477.6341
NTCA Reference Manual | 2024 / 2025
199
Chapter 8 | Thin-Bed Method Installations